| NFPA 25 |
National Fire Protection Association Inspection, Testing and Maintenance of Water-Based Fire Protection Systems. |
| NFPA 13 |
National Fire Protection Association Installation of Sprinkler Systems. |
| Accelerator |
A device used to accelerate the trip time in a dry system by channeling air into the intermediate chamber, thus destroying the pressure differential. Exception Vicataulic. |
| Alarm Valve |
A valve used on a wet system that has an intermediate chamber built into the valve that has ambient pressure. When water flows through the system, water enters the chamber, and flows through the bell line, allowing the electric bells or water motor gong to ring. |
| Antifreeze System |
A sprinkler system containing a mixture of water and antifreeze solution to prevent freezing. Operates same as a wet pipe system used in areas such as vestibules and loading docks in place of a dry pipe system. |
| Ball Valve |
A control valve used to isolate certain portions of a system. It only requires a quarter turn from fully open to fully closed. |
| Butterfly Valve |
An outside indicating valve used to isolate certain parts of a system. |
| Casing Relief Valve |
Located on the casing of a fire pump. During pump flow it helps to dissipate heat from the pump casing. |
| Check Valve |
A valve that allows water or air or any other substance to only fow in one direction. |
| Combined Standpipe & Sprinkler System |
Water piper outlets for use by the fire department and the automatic sprinklers. |
| Concealed Sprinkler Heads |
Covered by small metal plates and is flush with the ceiling. When heat from a fire increases, the plate falls away from the head. |
| Deluge System |
A sprinkler system that employs open sprinkler heads, a source of detection and a deluge valve. In the event of a fire, the detection system sends a signal, either electronically or pneumatically to the valve, releasing the valve, flowing water out of all open heads. |
| Dry Pipe System |
A system employing a dry pipe valve, air compressor or air source and associated piping. The dry pipe valve has air pressure above the dry seat and water below. In the event of a fire, a head fuses allowing the air pressure to reduce until the pressure differential is destroyed allowing water to flow into the system and out of the fused head. |
| Escutcheons |
Small metal discs that either cover or surround the sprinkler head. Escutcheons are used to seal gaps in the ceiling, maintain ratings and make sprinklers more aesthetically pleasing. |
| Electric Bell (Red) |
An alarm device mounted inside and outside to indicate a fire condition. |
| Exhauster |
A device used in conjunction with a dry pipe valve to accelerate the tripping of the dry pipe valve, either by pressurizing the intermediate chamber, exhausting the air pressure, or both. |
| FDC - Fire Department Connection |
Connection that the fire department can utilize to pump water into the system or standpipe to supplement the existing water supply. Also known as siamese connection or storz connection. |
| Fire Department Connection Caps |
Caps for the fire department connection to prevent items being placed that can block the flow of water. |
| Fire Pump |
Used to increase water flow and pressure. Driven by electric motor or diesel engine. |
| Foam System |
A sprinkler system that injects a solution of foam in the water to help suppress burning liquid fires. |
| Gate Valve |
OS&Y (Outside Screw and Yoke); A water control valve. |
| Gauge |
Located on the riser. It measures water or air pressure in a system. Must be replaced every five years. |
| Hangers |
Attached to building structure and are used to support fire protection piping. |
| Hose Station |
Contains the hose rack, hose nozzle, the hose and the hose connection. Can be used by the fire department to extinguish a fire. |
| Inspectors Test |
A valve located on the fire protection piping to activate the electrical alarm or water flow alarm. |
| Jockey Pump |
A small pump used in conjunction with a fire pump to maintain system pressure due to minimal leakage without causing high pressure surges. |
| Main Drain |
The primary drain connection located on the riser and also utilized as a flow test connections. |
| OS&Y - Outside Screw and Yoke |
This valve may be normally open or normally closed and requires a lock or supervision. Also known as Control Valve. |
| PIV - Post Indicator Valve |
Yard Post Indicator Valve - Self standing valve
Wall Post Indicator Valve - Wall mounted valve. This valve is normally open and requires a lock or supervision. Also known as Control Valve.
|
| Pre Action System |
A type of dry system actuated by smoke, heat, or fused sprinkler head which releases the pre action valve, filling the system with water. Used in freezers, computer and file rooms, etc. |
| Pressure Reducing Valve |
A device that reduces the water to a predetermined set point. |
| Private Fire Service Mains |
Water mains, usually with fire hydrants, that are not owned by a municipality. |
| Retard Chamber |
A device used to absorb pressure changes, thus reducing the chance of a nuisance sprinkler alarm. |
| Riser |
The piping immediately above the underground run-in, which incorporates the control valve, dry pipe valve, alarm value, pre action valve or deluge valve. |
| Shut off Valve |
A control valve used to stop water flow to the system or portions of the system. |
| Siamese Connection |
Connection that the fire department can utilize to pump water into the system or standpipe to supplement the existing water supply. Also known as fire departmen connection or storz connection. |
| Spare Head Box |
A small red box hanging on the wall near the sprinkler riser. The box contains a set of spare sprinkler heads and a sprinkler head wrench. Under 300 sprinklers = 6 heads, 300-1000 = 12 heads, 1000 or more = 24 heads. |
| Sprinkler Head |
A fusible link or glass bulb in the sprinkler head melts when the heat of the fire reaches a set temperature. Red/Orange Bulbs 135-170, Green/Yellow 175-225, Blue 250-300, Purple 325-375, Black 400-650. There are many different types if sprinkler heads made: Flush, Pendent, Recessed, Sidewall, Upright, Fast Response, Extended Coverage, Open Sprinklers, and Quick Response are just a few. The type of head used is determind by the hazard. |
| Sprinkler Head Wrench |
A special wrench designed to change sprinkler heads. There are many different wrenches for different types of heads. |
| Standpipe System |
Consists of piping, valves, and hose connections that can be discharged in streams or spray patterns through the attached hose and nozzle. |
| Tamper Switch |
A switch connected to the control valve and fire panel to indicate a closed valve, which will result in complete failure or diminished performance of that system. |
| Trip Test |
An annual test performent on a dry system for indication of dry pipe valve performance and water flow to the most remote points on the system. Maximum time (60) seconds or less. |
| Water Flow Switch |
A device mounted to the sprinkler systems to initiate an alarm at the fire panel upon flow of water. |
| Water Motor Gong |
A bell that sounds when water flows through the sprinkler system. This bell sounds when water flows against a water wheel by means of a small peto inside the bell. |
| Water Tank |
A tank that supplies water for the systems. |
| Wet Pipe System |
A sprinkler system containing water that discharges immediately when the sprinkler head is opened by the heat of the fire. |